Water Cooled Reciprocating Liquid Chiller


Condenser:
Water cooled condenser shell & tube type.
The shell is carbon steel and the tubes are integrally finned thick wall tubing of copper.
The attachment of tubes is made by expansion into grooved holes provided within the tube sheet.
Working pressures are: 30 bar refrigerant side 10 bar water side.

Compressors:
Semi Hermetic Compressor type, equipped with automatically reversible oil pump; refrigerant gas cooled type with built-in thermal protection, crankcase heater and large voltage capacity, suitable for 50-Hertz application. Each compressor is mounted on isolator pads and connected via flexible-vibration-absorbers to the rest of the cooper tubing to reduce vibration .
Transmission to the rest of the unit. Compressors are designed for high-energy efficiency, compact construction, and rugged reliability, long-life and are maintenance free. Compressors can be disassembled in the field for service. Oil level sight glass is standard. Oil electronic pressure control cuts the power to the motor when the pressure drops below acceptable limits.

Evaporator:
Direct expansion, shell and tube type with water flowing through the shell and the refrigerant through the tubes.
Design Working Pressures-shell (fluid) side is 150 psig ; tube (refrigerant) side is 300 psig.

Refrigerant Piping:
All circuits are made of brazed seamless copper tubes. Refrigerant circuits include :
1. Manual liquid line shut-off valve.
2. Automatic liquid line shut-off valve.
3. Refrigerant filter-drier.
4. Liquid sight glass/moisture indicator.
5. Liquid line solenoid valve.
6. Thermal expansion valve.
7. Permanent charging ports.
8. Liquid receiver.
9. External muffler.
10. Pressure-relief valve.

Controls:
A weatherproof cabinet harbors all indicator devices, switches, lamps, as well as most of the relays, contactors, circuit breakers, electric terminals, etc.

Power Compartment Controls includes:
- Compressor motor contactors.
- Compressor staging relays.

- Compressor crankcase heater relays.
- Control circuit terminals.
- Control circuit breaker (s).
- Field auxiliary control terminals.

Safety & Operating Controls includes:
- System on-off switch.
- Oil pressure cut off - manual reset.
- Refrigerant high pressure cut off - manual reset.
- Refrigerant low pressure cut off
- Thermostat - chilled liquid cycling.
- Freeze Stat - low liquid temperature cut off
- Timer - compressor delay.
- High and low voltage protection.
- Phase failure protection.

 
Water Cooled Chillers



Applications
:
are perfectly convenient for apartments, offices, small and large industries, hospitals, hotels, sports halls and mini or super stores. Units are especially patterned to meet modern design requirements and are suitable for vertical air flow.

Models: Standard COOLRITE Liquid Chillers have the following characteristics:

  • Size from 120 to 1270 .
  • Cooling & Heating Capacity
    from 17000 to 747800 BTU/hr.
  • Nominal Capacity from 14 to 625 tons.